Please select your category

 

ANSI/UL standards and specifications

In the following, reference is preferably made to national and international standards. The specifications mentioned there must be fully complied with. The associated verifications must be submitted with the offer.

 

The switchgear manufacturer has to run and furnish evidence of a certified quality management system according to EN/ISO 9001 and a certified environmental management system according to EN/ISO 14001.

 

Switchgear         IEC / EN standard   ANSI / UL

                   62271-1             __________

                   62271-200           __________

Switching devices  62271-100           __________

                   62271-102           __________

Voltage detecting

systems            62271-213           __________

                   62271-215           __________

Surge arresters    60099               __________

Degree of

protection         60529               __________

                   62262               __________

Insulation         60071               __________

Instrument

transformers       61869-1             __________

                   61869-2             __________

                   61869-3             __________

Insulating gas   62271-4             __________

Installation      61936-1             __________

Operation         EN 50110            __________

 

The switchgear must conform to the classifications according to IEC 62271-200.

Partition class: PM

Loss of service continuity category: LSC 2

 

Type of accessibility A

  • F Front
  • L Lateral
  • R Rear (for free-standing arrangement)